  DC Voltage

  52V

  Rated Current

  5A

  Current Range

  0 ~ 2.5A

  Rated Power

  260W

  Ripple & Noise (Max.)

  150mVp-p

  Voltage Adj. Range

  48 ~ 58V

  Voltage Tolerance

  ±1.0%

  Line Regulation

  ±0.5%

  Load Regulation

  ±0.5%

  Setup, Rise, Hold Up Time

  2000ms, 70ms, 50ms/400VAC
  2000ms, 70ms, 10ms/230VAC at Full Load

  Input Range

  200~240VAC

  Frequency Range

  47 ~ 63Hz

  Efficiency (Typ.)

  92% / 400V

  AC Current

  2.3A/230VAC

  Inrush Current (Max.)

  Cold Start 50A

  Leakage Current

  <3.5mA / 530VAC

  Overload

  105 ~ 130% Rated Output Power

  Over Voltage

  57 ~ 63V

  Over Temperature

  Shut Down O/P Voltage, Recovers Automatically After Temperature Goes Down

  DC OK Signal

  Relay Contact Rating(Max.) : 30V / 1A Resistive

  Working Temp

  -25 ~ +70° (Refer to «Derating Curve»)

  Working Humidity

  20 ~ 90% RH Non-Condensing

  Storage Temp., Humidity

  -40 ~ +85°, 10 ~ 95% RH

  Temp. Coefficient

  ±0.03% / °C (0 ~ 50°) °C

  Vibration

  Component: 10 ~ 500Hz, 2G 10Min./1Cycle, 60Min.Each Along X, Y, Z Axes; Mounting Clip: Compliance To Iec60068-2-6

  Safety Standards

  UL508, EAC TP TC 004 approved, IEC60950-1 CB approved by SIQ, design refer to GL;(meet EN60204-1)

  Withstand Voltage

  I/P-O/P:3KVAC   I/P-FG:2KVAC
  O/P-FG:0.5KVAC   O/P-DC OK:0.5KVAC

  Isolation Resistance

  I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25°C/ 70% RH

  EMC Emission

  Compliance to EN55011 (CISPR11), EN55032 (CISPR32), EN61204-3 Class B, EAC TP TC 020

  EMC Immunity

  Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020

  MTBF

  268K hrs min. MIL-HDBK-217F (25°C)

  Dimension

  125*65*92mm

  Packing

  0.65Kg; 20pcs/14Kg/1.16CUFT